indoor high voltage vacuum load switch CKFZ-12
Detailed Product Description
CKFZ-12D/630-20 type indoor high voltage vacuum load switch (hereinafter referred to as "load switch") and CKFZR-12D/T125-31.5 vacuum load switch - fuse combinations (hereinafter referred to as "GIS")were developed by comking at home and abroad advanced technology, self-developed three-phase AC 50Hz, rated voltage of 12kV indoor high-voltage power distribution switches for industrial and mining enterprises, high-rise buildings, residential quarters, schools, hospitals, stations, terminals and other distribution systems as indoor ring network of three-phase power supply equipment or terminal equipment.
Technical parameters
name | Units | switch | GIS | |
Rated voltage | kV | 12 | 12 | |
Rated Frequency | Hz | 50 | 50 | |
Rated Current | A | 630 | 125 | |
Short-circuit breaking current(Vacuum arc-extinguishing chamber) | A | 10000 | 10000 | |
Rated the expected short-circuit breaking current | kA |
| 31.5 | |
Rated cable charging breaking current | A | 20 | 20 | |
Rated short-circuit closing current (peak) | kA | 50 | 50 | |
Rated short-circuit breaking current (fuse) | kA |
| 31.5 | |
Rated short-term withstand current | kA | 20 |
| |
Rated peak withstand current | kA | 50 |
| |
Rated short-term withstand current duration (load switch) | s | 3 |
| |
Duration of Rated short-term withstand (earthing switch) | s | 2 |
| |
Rated breaking current transfer or transfer of current | A |
| 10000 | |
Rated Lightning Impulse withstand Voltage | Phase, relative to | kV | 75 | 75 |
Isolated fracture | kV | 85 | 85 | |
Vacuum arc-extinguishing chamber | kV | 75 | 75 | |
Rated short-time (1min) power-frequency withstandvoltage | Phase, relative to | kV | 42 | 42 |
Isolated fracture | kV | 48 | 48 | |
Vacuum arc-extinguishing chamber | kV | 42 | 42 | |
Mechanical life | times | 10000 | 10000 | |
Main circuit resistance | μΩ | ≤180 | ≤300 | |
temperature rise test Current | A | 630 | 125 | |
Linkage Test Release | times |
| 100 | |
Mechanical life of isolating switch | times | ≥2000 | ≥2000 | |
Mechanical life of the earth switch | times | ≥2000 | ≥2000 | |
switches classification by use | E2 | E2 | ||
Mechanical life according to the switch | M2 | M2 | ||
switch clearance between open contacts | mm | 10±1 | 10±1 | |
Load average gate switching opening speed | m/s | ≥0.8±0.2 | ≥0.8±0.2 | |
Average closing speed of the load switch | m/s | ≥0.6±0.2 | ≥0.6±0.2 | |
At different stages of three-phase reclosing | ms | ≤2 | ≤2 | |
Contact closing bounce time | ms | ≤3 | ≤3 | |
contact trip | mm | 4±1 | 4±1 | |
rated Contact pressure | N | 1000±200 | 1000±200 | |
indoor high voltage vacuum load switch CKFZ-12
Other Products from this Supplier
Company Info
Zhuhai Comking Electric Co., Ltd.
[China (Mainland)]
[Verified Member]
City: Zhuhai
Province/State: Guangdong
Country/Region : China (Mainland)
Business Type:Manufacturer
Online Postings: Products